Heat Pump Size Calculator: What Size Heat Pump Do I Need?
Enter your home and state to size a heat pump in tons, see the outdoor temperature where it stops keeping up, and find how many kW of backup heat to plan for.
Safety: Heat pump installation involves refrigerant, high-voltage wiring and, for backup heat strips, large electrical loads that need the right breaker and wire. Have a licensed HVAC contractor size and install the system.
A heat pump moves heat instead of making it, so it can heat and cool with the same equipment. Sizing one means balancing two loads. It has to be big enough to cool the house in summer without short-cycling, and it has to heat the house on cold days, when its output falls. This calculator works out both loads for your house and state, picks a size, and shows where the heat pump stops keeping up and how much backup heat fills the gap.
How it works
The cooling and heating loads use the same model as our AC size calculator. Heating adds slab-edge losses and higher winter air leakage, and it takes no credit for sun, people or appliances. The heat pump side works like this:
size smallest unit covering 95% of the cooling load
(or of the heating load at the design temperature, if you choose)
output(T) rated × (1 − slope × (47 °F − T))
standard: 100% at 47 °F, 60% at 17 °F
cold-climate: 100% at 47 °F, 75% at 5 °F
heat loss(T) UA × (70 °F − T)
balance point the T where output(T) = heat loss(T)
backup (kW) (heat loss − output) at the design temperature ÷ 3,412
Capacity in the cold. Heat pump output is rated at 47 °F and drops as it gets colder outside. We use straight-line curves: a standard heat pump keeps 60% of its rated output at 17 °F, and a cold-climate model keeps 75% at 5 °F, above NEEP’s 70% minimum. Real units vary, and the manufacturer’s extended performance data is the place to check a specific model.
Heating design temperature. It’s the lowest hourly 10th-percentile temperature from December through February in NOAA’s 1991–2020 normals, at the station nearest a major city in your state.
Sizing for heating picks the smallest size whose output at the design temperature covers the heat loss. In cold places that can mean a much bigger unit than the cooling load needs. That works with variable-speed equipment, but a single-speed unit that large will short-cycle in summer.
Worked example
A two-story, 1,800 sq ft house in Minneapolis has good insulation, low-E windows and ducts in the attic. NOAA normals at MSP give a heating design temperature of −9 °F.
- Cooling load: about 18,200 BTU/h, so a 1.5-ton heat pump covers it
- Heat loss: about 35,300 BTU/h at −9 °F (446 BTU/h per °F of indoor–outdoor difference)
- Standard heat pump: at −9 °F it puts out about 4,600 BTU/h. The balance point is about 36 °F, and you’d need about 9 kW of backup heat
- Cold-climate heat pump, same size: 12,000 BTU/h at −9 °F, a balance point near 33 °F and about 7 kW of backup
- Sized for heating, a cold-climate unit has to be 5 tons to cover −9 °F on its own. Most owners in this climate choose a 2 to 3-ton cold-climate model and keep 5 to 7 kW of backup
Heat pump balance point by state: reference table
The same 2,000 sq ft home in every state, with a standard heat pump sized for cooling and the backup heat each type needs at the heating design temperature.
| State (station) | Heating design | Size | Balance point, standard | Backup, standard | Backup, cold-climate |
|---|---|---|---|---|---|
| Alabama (Birmingham AP, AL) | 20 °F | 3 t | 29 °F | 3 kW | 1 kW |
| Alaska (Anchorage Merrill Fld, AK) | -8 °F | 2 t | 38 °F | 14 kW | 11 kW |
| Arizona (Phoenix Sky Harbor Intl AP, AZ) | 38 °F | 3.5 t | 25 °F | 0 kW | 0 kW |
| Arkansas (Little Rock AP Adams Fld, AR) | 21 °F | 3 t | 29 °F | 3 kW | 1 kW |
| California (Los Angeles Intl AP, CA) | 44 °F | 2.5 t | 33 °F | 0 kW | 0 kW |
| Colorado (Aurora Buckley Fld ANGB, CO) | 9 °F | 2.5 t | 33 °F | 8 kW | 6 kW |
| Connecticut (Hartford Bradley Intl AP, CT) | 4 °F | 3 t | 29 °F | 9 kW | 5 kW |
| Delaware (Philadelphia Intl AP, PA) | 14 °F | 3 t | 29 °F | 5 kW | 3 kW |
| District of Columbia (Washington Reagan AP, VA) | 18 °F | 3 t | 29 °F | 4 kW | 2 kW |
| Florida (Jacksonville NAS, FL) | 34 °F | 3 t | 29 °F | 0 kW | 0 kW |
| Georgia (Atlanta Fulton Co AP, GA) | 21 °F | 3 t | 29 °F | 3 kW | 1 kW |
| Hawaii (Honolulu Intl AP, HI) | 63 °F | 3 t | 29 °F | 0 kW | 0 kW |
| Idaho (Boise Air Terminal, ID) | 14 °F | 3 t | 29 °F | 5 kW | 3 kW |
| Illinois (Chicago Midway AP, IL) | 4 °F | 3 t | 29 °F | 9 kW | 5 kW |
| Indiana (Indianapolis, IN) | 5 °F | 3 t | 29 °F | 8 kW | 5 kW |
| Iowa (Des Moines Intl AP, IA) | -2 °F | 3 t | 29 °F | 11 kW | 7 kW |
| Kansas (Wichita, KS) | 11 °F | 3.5 t | 25 °F | 6 kW | 2 kW |
| Kentucky (Louisville Intl AP, KY) | 13 °F | 3 t | 29 °F | 6 kW | 3 kW |
| Louisiana (New Orleans Lakefront AP, LA) | 36 °F | 3 t | 29 °F | 0 kW | 0 kW |
| Maine (Portland Intl Jetport, ME) | 0 °F | 2.5 t | 33 °F | 11 kW | 8 kW |
| Maryland (Baltimore Wash Intl AP, MD) | 14 °F | 3 t | 29 °F | 5 kW | 3 kW |
| Massachusetts (Boston Logan Intl AP, MA) | 8 °F | 2.5 t | 33 °F | 8 kW | 6 kW |
| Michigan (Detroit City AP, MI) | 8 °F | 2.5 t | 33 °F | 8 kW | 6 kW |
| Minnesota (Minneapolis/St Paul AP, MN) | -9 °F | 2.5 t | 33 °F | 14 kW | 10 kW |
| Mississippi (Jackson Intl AP, MS) | 24 °F | 3 t | 29 °F | 2 kW | 0 kW |
| Missouri (Kansas City Downtown AP, MO) | 9 °F | 3 t | 29 °F | 7 kW | 4 kW |
| Montana (Billings Logan Intl AP, MT) | -1 °F | 3 t | 29 °F | 10 kW | 7 kW |
| Nebraska (Omaha Eppley Airfield, NE) | 0 °F | 3 t | 29 °F | 10 kW | 6 kW |
| Nevada (Las Vegas Mccarran AP, NV) | 32 °F | 3.5 t | 25 °F | 0 kW | 0 kW |
| New Hampshire (Manchester AP, NH) | 1 °F | 2.5 t | 33 °F | 10 kW | 7 kW |
| New Jersey (Newark Intl AP, NJ) | 13 °F | 3 t | 29 °F | 6 kW | 3 kW |
| New Mexico (Albuquerque Intl AP, NM) | 19 °F | 3 t | 29 °F | 4 kW | 2 kW |
| New York (New York Laguardia AP, NY) | 15 °F | 3 t | 29 °F | 5 kW | 3 kW |
| North Carolina (Charlotte Douglas AP, NC) | 21 °F | 3 t | 29 °F | 3 kW | 1 kW |
| North Dakota (Fargo Hector Intl AP, ND) | -16 °F | 2.5 t | 33 °F | 16 kW | 12 kW |
| Ohio (Columbus Port Columbus Intl AP, OH) | 7 °F | 3 t | 29 °F | 8 kW | 5 kW |
| Oklahoma (Oklahoma City Will Rogers AP, OK) | 18 °F | 3.5 t | 25 °F | 3 kW | 0 kW |
| Oregon (Portland Intl AP, OR) | 29 °F | 2.5 t | 33 °F | 2 kW | 1 kW |
| Pennsylvania (Philadelphia Intl AP, PA) | 14 °F | 3 t | 29 °F | 5 kW | 3 kW |
| Rhode Island (Providence T F Green AP, RI) | 8 °F | 2.5 t | 33 °F | 8 kW | 6 kW |
| South Carolina (Charleston Intl AP, SC) | 27 °F | 3 t | 29 °F | 1 kW | 0 kW |
| South Dakota (Sioux Falls, SD) | -8 °F | 3 t | 29 °F | 13 kW | 8 kW |
| Tennessee (Nashville Intl AP, TN) | 16 °F | 3 t | 29 °F | 5 kW | 2 kW |
| Texas (Houston Intercont AP, TX) | 32 °F | 3.5 t | 25 °F | 0 kW | 0 kW |
| Utah (Salt Lake City Intl AP, UT) | 14 °F | 3 t | 29 °F | 5 kW | 3 kW |
| Vermont (Burlington Intl AP, VT) | -7 °F | 2.5 t | 33 °F | 13 kW | 9 kW |
| Virginia (Oceana NAS, VA) | 23 °F | 3 t | 29 °F | 2 kW | 1 kW |
| Washington (Seattle Boeing Fld, WA) | 28 °F | 2.5 t | 33 °F | 2 kW | 1 kW |
| West Virginia (Charleston Yeager AP, WV) | 11 °F | 3 t | 29 °F | 6 kW | 4 kW |
| Wisconsin (Milwaukee Mitchell AP, WI) | 1 °F | 2.5 t | 33 °F | 10 kW | 7 kW |
| Wyoming (Cheyenne, WY) | 7 °F | 2.5 t | 33 °F | 9 kW | 6 kW |
Tips and common mistakes
Choose a cold-climate model where winters are cold. In zones 5 to 7, the difference between a standard and a cold-climate heat pump is often several kW of strip heat on the coldest nights, and strip heat costs about three times as much to run.
Look at the 5 °F and 17 °F capacities. Rated tons only tell you about mild weather. Ask for the model’s output at your design temperature.
Size the backup heat and the electrical service together. A 10 kW strip heater draws about 42 amps at 240 volts. Make sure your panel can carry it.
Keep a dual-fuel option in mind. Pairing a heat pump with a gas furnace lets the furnace take over below the balance point, which can make sense where gas is cheap.
Fix the envelope first. Every BTU of heat loss you remove lowers the balance point. In cold climates, air sealing and insulation often matter more than equipment.
Frequently asked questions
How do I size a heat pump?
Start with the cooling load, because a heat pump is an air conditioner that can run in reverse. Then check the heating side. At your coldest design temperature, a heat pump puts out much less than its rated capacity, so you need backup heat, a cold-climate model or a larger unit to cover the gap.
What is a heat pump balance point?
It's the outdoor temperature where the heat pump's output exactly matches the house's heat loss. Above it, the heat pump heats the house on its own. Below it, backup heat makes up the difference. Lower balance points mean less backup heat and lower bills.
Do heat pumps work in cold climates?
Yes, if you choose a cold-climate model. Under NEEP's specification, cold-climate heat pumps have to deliver at least 70 percent of their rated capacity at 5 °F, and many keep running well below 0 °F. Standard heat pumps lose capacity much faster in the cold.
How much backup heat does a heat pump need?
Enough to cover the difference between the heat loss and the heat pump's output at your heating design temperature. In mild climates that can be zero. In northern states, a standard heat pump sized for cooling can need 5 to 10 kW or more of electric strip heat. A cold-climate model needs less.
Should I size my heat pump for heating or cooling?
In cooling-dominated climates, size for cooling. In cold climates, a slightly larger variable-speed cold-climate unit can cover most of the heating load while still running at low speed in summer to control humidity. A single-speed unit sized for heating will be oversized for cooling.